API · ASME · DIN · EN 標準工業閥門
雙調節平衡閥(DRV)
雙調節閥是帶標定手輪與確定止動的靜態平衡閥:設定值可預置、鎖定並重新打開至完全相同的位置——這正是水力調試所需。產品範圍涵蓋青銅 PN25 系列 DN15 至 DN50(含 DN15 小流量變體)與球墨鑄鐵 PN16 系列 DN65 至 DN600,齒輪驅動(DN50-DN600)與手柄驅動(DN65-DN150)變體,端接為法蘭或 BS EN 10226 錐形/平行螺紋。選型取決於管徑與流量、系統對青銅或球墨鑄鐵、安裝位置的手輪操作,以及記憶止動設定範圍。多來源資料補充運行框架:英式術語「雙調節」指經記憶止動在關閉後可精確恢復設定位置、在三通混合/分流閥旁路中產生流阻的主要任務、Y 型截止閥體全開時壓損最小、VODRV 的 Kv 對 delta-P 設定法(最小設定點附近精度 ±15%)、FODRV 調試閥以固定 Kvs 孔口或文丘里測量(典型精度 +5%)、低壓差系統的文丘里壓力回收、遵守閥體流向箭頭的單向安裝、模擬未來系統負荷的 DRV 旁通,以及以 PICV 取代調試閥的變流量趨勢。
屬於 平衡閥 系列
最後更新: 2026-11
系列規格
| Nominal valve connection size | DN50 to DN150 |
|---|---|
| Pressure class / nominal rating designation | Class 150, PN16 |
| End connection types | End Connections Flanged |
| Valve body material | Bronze, Ductile Iron |
| Design standards | DIN EN 13709, DIN 3356 |
| Inspection and pressure-test standards | EN 12266-1 |
| bronze line | D921 DN15 to DN50 Double Regulating Valve (DRV) – Bronze PN25 |
| bronze low flow variant | D923 DN15 Low Flow Double Regulating Valve (DRV) |
| ductile line | DM921 DN65 to DN300 Double Regulating Valve (DRV) – Ductile Iron PN16 |
| Gearbox variant | DM925G / DM925L DN50 to DN600 1/4 Turn Gearbox Operated Double Regulating Valve (DRV) – Ductile Iron PN16 |
| Lever variant | DM925LW DN65 to DN150 Lever Operated Double Regulating Valve (DRV) – Ductile Iron PN16 |
| threaded connections | Sizes 1" to 2" taper threaded to BS EN 10226-2 (ISO 7-1) formerly BS 21 |
| memory stop principle | a valve capable of being set to a desired degree of opening, locking that position with a memory stop to ensure the position can be retrieved exactly after the valve has been closed. |
| bypass duty 3port | In the UK the Double Regulating Valve [DRV] is primarily used to create flow resistance or a pressure drop in the by-pass of a 3-Port mixing or diverter valve or for simulating a load for a future loop. |
| no flow measurement | Keep in mind that this balancing valve doesn’t provide any flow measurement. |
| butterfly memory stop ref | For line sizes from DN 65, Butterfly valves that have been fitted with a memory stop can offer the same functionality as the traditional globe design while being lighter, smaller, easier to install and less costly. |
| vodrv definition | The DRV is sometimes referred to as “ Variable Orifice Double Regulating Valve ” [VODRV]. |
| vodrv kv method | The flow rate is calculated using the Kv value for each handwheel setting and the Δ P across the valve. |
| vodrv accuracy ref | The measurement accuracy may be adversely affected by this principle by plus or minus 15%, when close to the minimum set point (25% open as per CIBSE guideline). |
| vodrv unidirectional | The valve is unidirectional and the direction of the flow arrow on the valve body must be respected. |
| fodrv definition | The Fixed Orifice Double Regulating Valve [FODRV] is also referred to as Commissioning Valve or Commissioning Valve Set. |
| fodrv accuracy ref | The accuracy of this type of valve is typically + 5%, depending on the opening position. |
| venturi pressure recovery | The FODRV with venturi minimises turbulence and recovers a significant proportion of the pressure loss after flow has passed through it, and can be close coupled, which makes the venturi FODRV suitable for systems with low differential pressure. |
| picv variable flow trend | Commissioning Valves are not suitable for variable flow and have been replaced by PICVs. |
| bypass future load | Install a DRV bypass between flow and return to simulate future system load. |
| y pattern globe body | Typically this valve is a Y pattern globe valve arranged in this way to present the smallest pressure loss to the system when fully open. |
| double regulating meaning | The description DOUBLE regulating means that it has a feature whereby you can set the position that the valve is to operate at in such a way that you can still close the valve for maintenance purposes. |
| resistance reduces flow | Adjustment of this valve will add resistance to the system and hence reduce the flow. |
| peer fodrv line | Peer FODRV execution: fixed-orifice commissioning valve in corrosion-resistant brass with brass test points, screwed female BSP, PN25, -10°C to 120°C |
| peer vodrv line | Peer VODRV execution: variable-orifice double regulating valve in ductile iron, flanged PN16, -10°C to 120°C, supplied with 2 test points |
| Source 1 — venturi valve construction | Balancing valve for hydraulic systems. Flow meter with Venturi device. Stainless steel obturator. Complete with quick-fit pressure test ports. |
| Source 1 — Valve body material | Material : dezincification resistant brass DR |
| Source 1 — Service temperature range | Medium temperature range : -20–120 °C |
| Source 1 — Maximum working pressure | Maximum working pressure : 16 bar |
| Source 1 — glycol limit | Maximum percentage of glycol : 50 % |
| Source 2 — memory stop principle | Memory stop/Sealing locking The valves are equipped with an adjustment position memory system that, after full closure which can be necessary for various reasons, allows easy re-opening at the initial position. |
| Source 2 — setting seal locking | There are two holes on the knob that can be used to seal (5) the setting position to avoid or detect any tampering over time. |
| Source 2 — presetting method | Knowing the value of the pressure drop p that needs to be created by the valve with a certain flow rate G, you can obtain the adjustment position number for the knob (PRESETTING). |
| Source 2 — adjustment scale | clockwise turn of the knob moves the red indicator by one step, from position 0 (valve closed) to position 6 (fully open valve). In addition, the decimal graduations of the black micrometric scale enable further refining of the adjustment. |
| Source 2 — installation clearance | The balancing valves must be installed in such a way as to ensure free access to the pressure test ports, drain cocks and the adjustment knob. The valves can be fitted on either horizontal or vertical pipes. |
| Source 3 — fodrv definition | is a fixed orifice double regulating valve (FODRV) which uses a venturi to measure the flow of liquid passing through the valve. |
| Source 3 — venturi definition | A venturi is a fixed orifice device consisting of two different diameters with a tapered section between them. The smaller diameter is referred to as the throat. |
| Source 3 — venturi upstream | The venturi is located upstream of the double regulating valve which provides stable flow measurement during flow regulation. |
| Source 3 — Valve body material | Component Material Grade Body DZR alloy BS EN 12165 CW602N Cover DZR alloy BS EN 12165 CW511L Stem DZR alloy BS EN 12164 CW724R Regulating disc Stainless steel AISI 303 Seal seat DZR alloy BS EN 12165 CW602N Disc seal PTFE Seals EPDM rubber |
| Source 3 — memory stop restriction | The valves are equipped with an adjustable memory stop that, after full closure allows easy re-opening to the set position. |
| Source 3 — position indicator | The valve position is indicated by 2 digits on the upper side of the handwheel, one digit indicates the number of full turns from closed (6) and the second indicating the partial turn (10). |
| Source 3 — technical data | Number of adjustment turns: 6 Female connecting threads: BS EN 288-1 |
| Source 3 — stem seal design | The double `O' ring stem seal (3) prevents water coming into contact with the actuating thread of the stem and causing leakage. |
| Source 4 — threaded size range | Threaded version sizes DN 15 (1/2"), DN 20 (3/4"), DN 25 (1"), DN 32 (1 1/4"), DN 40 (1 1/2"), DN 50 (2") |
| Source 4 — flanged size range | Flanged version sizes DN 65, DN 80, DN 100, DN 125, DN 150, DN 200, DN 250, DN 300 |
| Source 4 — flange standard | DN 65, 80, 100, 125, 150, 200, 250, 300; PN 16 - EN 1092-2 |
| Source 5 — venturi valve role | Venturi valves provide balance, ease of commissioning, and shut-off in a wide range of HVAC systems. |
| Disc Materials | Ductile Iron, SS304, SS316, Bronze |
| shaft materials | SS410, SS431 |
| seat ring materials | EPDM, NBR |
| o ring materials | EPDM, NBR |
| bushing materials | PTFE, Bronze |
| flanged end standard | EN 1092-1 PN25 |
| Face-to-face dimensional standard | EN 558-1 |
範圍與來源備註
| measurement accuracy | Measurement accuracy: reference VODRV principle can drift plus or minus 15% near the minimum set point (25% open per CIBSE), while the tenant page presents a calibrated handwheel with no stated measurement accuracy - accuracy class is unstated on the tenant page. |
|---|---|
| line size alternative | Line-size alternative: reference practice offers butterfly valves with memory stops as functionally equivalent from DN 65 upward (lighter, smaller, cheaper), while the tenant globe-design DRV lines run DN65 to DN600 - the globe-versus-butterfly split is not represented on the tenant page. |
| system trend positioning | System-trend positioning: reference guidance states commissioning valves are not suitable for variable flow and have been replaced by PICVs, while the tenant page positions static balancing DRVs without the variable-flow caveat. |
| peer pressure material mix | Peer pressure/material mix: peer executions offer PN20 brass screwed FODRV lines and PN16 flanged ductile-iron VODRV lines, versus the tenant PN25 bronze and PN16 ductile-iron lines - peer brass PN20 sits between the tenant bronze PN25 and ductile PN16 bands. |
訂購與文件
文件
請在詢問時一併說明您需要的文件組合——此結構的常見項目(材質證明、按所列檢驗標準的測試報告、尺寸圖)將於報價時確認並隨附供應。
報價
可直接報價的詢問應說明:公稱口徑與壓力額定、閥體與閥座材質偏好、端部連接、操作方式,以及含溫度的使用介質。本頁的典型值為基準參考範圍;具有約束力的數值於報價時確認。
樣品與供應
供應條件、訂購數量與交期按訂單議定——請在詢問時說明目的地國家與所需時程。
儲存與運輸
閥門儲存時應保護閥座與密封件免受紫外線、臭氧與變形影響,安裝前保留端面保護蓋;彈性體或 PTFE 閥座結構應避免長期戶外存放——閥座材料在陽光直射與冰凍條件下老化最快。
常見問題
雙調節平衡閥(drv)的報價詢問應包含哪些內容?
執行標準與壓力等級、公稱口徑、閥體與閥座材質、介質及溫度、目的地——缺失的資訊會在報價過程中確認。
雙調節平衡閥(drv)提供哪些口徑與壓力等級?
本頁面尚未公布該閥門經驗證的口徑與壓力等級範圍——適用於您工況的口徑與壓力等級會在報價過程中提出並確認。請在詢問時附上工況條件,選型結果會在報價中說明。
雙調節平衡閥(drv)提供哪些閥體材質?
本頁面尚未公布該閥門經驗證的閥體材質範圍——適用於您工況的閥體材質會在報價過程中提出並確認。請在詢問時附上工況條件,選型結果會在報價中說明。