規格
| Nominal valve connection size | DN65 to DN300 |
|---|---|
| Pressure Rating | PN16 |
| Service temperature range | 10 to 120 °C |
| End connection types | Flanged |
| Valve body material | Ductile Iron |
| flow measurement | Two integral pressure test points for flow measurement, regulation and isolation; Y-pattern globe body |
| measurement accuracy | ±10% at the full open position |
| accuracy standard | Accuracy reduction at partial openings per BS 7350 |
| regulating feature | Isolation duty with reopening to the pre-set balancing position |
應用與選型指引
Select this execution for medium and large HVAC heating and cooling circuits where a variable orifice readout is acceptable and isolation duty is needed at the same branch point - the double regulating feature is the reason to prefer it over a plain balancing valve at pump manifolds, risers and major branches. Verify the target flow against the published flow measurement graphs for the size, and remember that readout accuracy degrades at partial openings in accordance with BS 7350, so size the valve to operate near open where possible.
常見問題
Why choose a variable orifice double regulating valve instead of a fixed orifice design?
The variable orifice execution measures flow across the full valve travel and covers DN65 to DN300 at PN16, which makes it the practical choice on larger ductile-iron pipework where a bronze fixed orifice range ends at DN50. The trade is accuracy: plus or minus 10 percent at the full open position, with some reduction at partial openings per BS 7350, versus the tighter accuracy of integral fixed orifice designs - so large branches suit this execution and small circuits suit fixed orifice.
What does the double regulating feature actually do during commissioning?
It couples a memory stop to the regulating spindle: the valve can be fully closed for isolating the branch during the rest of commissioning, and when reopened it stops at exactly the pre-set balancing position. The balanced flow setting is therefore retained without re-measuring after any isolation event, which is what makes the valve usable as both an isolation point and a balancing point.
What information is needed to quote and size this valve?
The design flow rate and the size (DN65 to DN300) so the flow measurement graphs can be checked for a workable readout, the system pressure class (PN16 flanged), the medium temperature within 10-120 C, and whether injection or circuit duty applies. With those points the readout quality and the pre-set position can both be fixed in one pass.
訂購與文件
文件
請在詢問時一併說明您需要的文件組合——此結構的常見項目(材質證明、按所列檢驗標準的測試報告、尺寸圖)將於報價時確認並隨附供應。
報價
可直接報價的詢問應說明:公稱口徑與壓力額定、閥體與閥座材質偏好、端部連接、操作方式,以及含溫度的使用介質。本頁的典型值為基準參考範圍;具有約束力的數值於報價時確認。
樣品與供應
供應條件、訂購數量與交期按訂單議定——請在詢問時說明目的地國家與所需時程。
儲存與運輸
閥門儲存時應保護閥座與密封件免受紫外線、臭氧與變形影響,安裝前保留端面保護蓋;彈性體或 PTFE 閥座結構應避免長期戶外存放——閥座材料在陽光直射與冰凍條件下老化最快。